Drain Cable

          
Application :
Ideal for irrigation pumps, drinking water supply pumps, sewage treatment plants, sea water / river water handling equipment.
Standards :
IS : 694 , BS 6500
Conductor :
Class 5 plain stranded flexible copper conductors to IS : 8130 or  BS EN 60228:2005 (previously BS6360), VDE0295.
Insulation :
PVC (Polyvinyl Chloride)
Sheath :
PVC (Polyvinyl Chloride)
Sheath Colour :
Black , Gray , Yellow , Blue
Voltage Rating :
Up to 1100 Volts.
Temperature Rating :
700c
Requirement of Oxygen to Catch Fire (% in air)
> 30
Temperature Required to catch fire ( with 21% oxygen)
> 2500 C.
Visibility during Cable burning (%) :
< 35
 
 (1) Copper Conductor (2) PVC Insulation of Cores ( Red, yellow , blue )
 (3) PVC Sheath
4 Core Flat Cables as per IS : 694
Conductor Overall Dimensions Current carrying capacity @400 C. Amps.
Area
Sq.mm.
No. of Cond. / Dia. mm Width (Approx.)  ‘W’ mm Height (Approx.)  ‘H’ mm
1.5 22 / 0.30* 15.8 6.0 14
2.5 36 / 0.30* 18.0 6.5 18
* As per Conductor Class 2 of IS : 8130 : 1984
4.0 56 / 0.30 21.0 7.6 26
6.0 84 / 0.30 24.3 7.9 31
10.0 140 / 0.30 29.7 9.9 42
16.0 226 / 0.30 36.0 11.8 57
25.0 354 / 0.30 45.0 14.7 72
35.0 495 / 0.30 50.1 16.2 90
50.0 703 / 0.30 58.1 18.3 115
70.0 360 / 0.50 66.5 20.0 143
95.0 475 / 0.50 77.3 23.5 165
** The No. of wires and Strand Dia. Will be such as to satisfy the     Requirement of conductor resistance as per IS : 8130 , IEC 60228 DIN VDE 0295 , BS 6360
 
PVC INSULATED DOUBLE SHEATHED ROUND SUBMERSIBLE CABLES :
Application :
Double sheathed round 3 core and 4 core cables are ideally suited for heavy duty application like sewage , slurry and dewatring pumps in which the sheathing must be able to withstand abrasion, preventingress of water along the interstices of the cable, and be resistant to acidic fluids & reactive base chemicals.
Conductor Redial Thickness of Insulation Nom.
mm
Thickness of Inner Sheath Nom.
mm
Thickness of Outer Sheath Nom.
Mm
Overall Diameter Approx.
mm
Current carrying capacity @400 C. Amps
Area
Sq.mm
No. of Strands / Nom. Dia. 3 Core 4 Core 3 Core 4 Core 3 Core 4 Core
1.5 30 / 0.25 0.6 1.0 1.0 1.2 1.2 10.8 12.0 14
2.5 50 / 0.25 0.7 1.0 1.0 1.2 1.2 13.2 13.8 18
4.0 56 / 0.30 0.8 1.0 1.0 1.2 1.4 14.2 15.5 26
6.0 84 / 0.30 0.8 1.0 1.0 1.4 1.4 16.5 18.5 31
10.0 140 / 0.30 1.0 1.0 1.0 1.4 1.4 19.1 22.0 42
16.0 226 / 0.30 1.0 1.0 1.0 1.4 1.4 23.5 25.0 57
25.0 354 / 0.30 1.2 1.0 1.0 1.6 1.6 28.5 31.0 72
35.0 495 / 0.30 1.2 1.0 1.0 2.0 2.0 30.5 32.8 90
 
 
Rating factors for low Voltage :
Multiply the full load current of submersible motors by factors given below for different supply voltages & select the right cable.
Voltage 415 400 350 300 275 250
Rating Factor 1 1.05 1.15 1.25 1.30 1.35
 
Derating Factors :
Multiply the full load current of submersible motors by factors given below for various ambient temperatures.
Ambient Temperature C. 30 35 40 45 50
Rating Factor 1.09 1.04 1.00 0.95 0.77
 