Drain Cable |
|
 |
| Application : |
| Ideal for irrigation pumps, drinking water supply pumps, sewage treatment plants, sea water / river water handling equipment. |
| Standards : |
| IS : 694 , BS 6500 |
| Conductor : |
| Class 5 plain stranded flexible copper conductors to IS : 8130 or BS EN 60228:2005 (previously BS6360), VDE0295. |
| Insulation : |
| PVC (Polyvinyl Chloride) |
| Sheath : |
| PVC (Polyvinyl Chloride) |
| Sheath Colour : |
| Black , Gray , Yellow , Blue |
| Voltage Rating : |
| Up to 1100 Volts. |
| Temperature Rating : |
| 700c |
| Requirement of Oxygen to Catch Fire (% in air) |
| > 30 |
| Temperature Required to catch fire ( with 21% oxygen) |
| > 2500 C. |
| Visibility during Cable burning (%) : |
| < 35 |
|
|
(1) Copper Conductor (2) PVC Insulation of Cores ( Red, yellow , blue )
(3) PVC Sheath |
| 4 Core Flat Cables as per IS : 694 |
| Conductor |
Overall Dimensions |
Current carrying capacity @400 C. Amps. |
Area
Sq.mm. |
No. of Cond. / Dia. mm |
Width (Approx.) ‘W’ mm |
Height (Approx.) ‘H’ mm |
| 1.5 |
22 / 0.30* |
15.8 |
6.0 |
14 |
| 2.5 |
36 / 0.30* |
18.0 |
6.5 |
18 |
| * As per Conductor Class 2 of IS : 8130 : 1984 |
| 4.0 |
56 / 0.30 |
21.0 |
7.6 |
26 |
| 6.0 |
84 / 0.30 |
24.3 |
7.9 |
31 |
| 10.0 |
140 / 0.30 |
29.7 |
9.9 |
42 |
| 16.0 |
226 / 0.30 |
36.0 |
11.8 |
57 |
| 25.0 |
354 / 0.30 |
45.0 |
14.7 |
72 |
| 35.0 |
495 / 0.30 |
50.1 |
16.2 |
90 |
| 50.0 |
703 / 0.30 |
58.1 |
18.3 |
115 |
| 70.0 |
360 / 0.50 |
66.5 |
20.0 |
143 |
| 95.0 |
475 / 0.50 |
77.3 |
23.5 |
165 |
| ** The No. of wires and Strand Dia. Will be such as to satisfy the Requirement of conductor resistance as per IS : 8130 , IEC 60228 DIN VDE 0295 , BS 6360 |
|
|
| |
| PVC INSULATED DOUBLE SHEATHED ROUND SUBMERSIBLE CABLES : |
Application :
Double sheathed round 3 core and 4 core cables are ideally suited for heavy duty application like sewage , slurry and dewatring pumps in which the sheathing must be able to withstand abrasion, preventingress of water along the interstices of the cable, and be resistant to acidic fluids & reactive base chemicals. |
 |
| Conductor |
Redial Thickness of Insulation Nom.
mm |
Thickness of Inner Sheath Nom.
mm |
Thickness of Outer Sheath Nom.
Mm |
Overall Diameter Approx.
mm |
Current carrying capacity @400 C. Amps |
Area
Sq.mm |
No. of Strands / Nom. Dia. |
3 Core |
4 Core |
3 Core |
4 Core |
3 Core |
4 Core |
| 1.5 |
30 / 0.25 |
0.6 |
1.0 |
1.0 |
1.2 |
1.2 |
10.8 |
12.0 |
14 |
| 2.5 |
50 / 0.25 |
0.7 |
1.0 |
1.0 |
1.2 |
1.2 |
13.2 |
13.8 |
18 |
| 4.0 |
56 / 0.30 |
0.8 |
1.0 |
1.0 |
1.2 |
1.4 |
14.2 |
15.5 |
26 |
| 6.0 |
84 / 0.30 |
0.8 |
1.0 |
1.0 |
1.4 |
1.4 |
16.5 |
18.5 |
31 |
| 10.0 |
140 / 0.30 |
1.0 |
1.0 |
1.0 |
1.4 |
1.4 |
19.1 |
22.0 |
42 |
| 16.0 |
226 / 0.30 |
1.0 |
1.0 |
1.0 |
1.4 |
1.4 |
23.5 |
25.0 |
57 |
| 25.0 |
354 / 0.30 |
1.2 |
1.0 |
1.0 |
1.6 |
1.6 |
28.5 |
31.0 |
72 |
| 35.0 |
495 / 0.30 |
1.2 |
1.0 |
1.0 |
2.0 |
2.0 |
30.5 |
32.8 |
90 |
|
| |
| |
| Rating factors for low Voltage : |
| Multiply the full load current of submersible motors by factors given below for different supply voltages & select the right cable. |
| Voltage |
415 |
400 |
350 |
300 |
275 |
250 |
| Rating Factor |
1 |
1.05 |
1.15 |
1.25 |
1.30 |
1.35 |
|
| |
| Derating Factors : |
| Multiply the full load current of submersible motors by factors given below for various ambient temperatures. |
| Ambient Temperature C. |
30 |
35 |
40 |
45 |
50 |
| Rating Factor |
1.09 |
1.04 |
1.00 |
0.95 |
0.77 |
|