Power & Control Cables |
|
|
TABLE -1
1.5 Sq.mm., Solid Copper Conductor, PVC insulated, PVC Sheathed,
Unarmoured(YY)/Armoured (YWY & YFY), Multi Core Control Cables -
650/ 1100 Volts Conforming to IS : 1554 (I) 1988
|
|
Unarmoured |
Armoured |
Max DC
Conductor
Resistance
at 20* C
0hm/km |
A.C. Current Rating |
No.of
Crores |
Nominal
Thickness
of PVC
Insulation
mm |
Approx.
Over all Diameter
mm |
Approx.
Over all
Weight
kg/km |
Normal
steel
Armour
Size
mm
W F |
Approx.
Over all
Diameter
mm |
Approx.
Over all
Weight
kg/km |
In Air |
In Ground |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
2 |
0.8 |
10.4 |
180 |
1.4 |
12.8 |
420 |
12.1 |
20 |
24 |
23 |
27 |
3 |
0.8 |
11.0 |
198 |
1.4 |
13.5 |
440 |
12.1 |
17 |
21 |
21 |
24 |
4 |
0.8 |
11.9 |
230 |
1.4 |
14.1 |
490 |
12.1 |
17 |
21 |
21 |
24 |
5 |
0.8 |
12.8 |
278 |
1.4 |
14.8 |
580 |
12.1 |
14 |
17 |
17 |
19 |
6 |
0.8 |
13.4 |
325 |
1.4 |
16.0 |
650 |
12.1 |
13 |
16 |
15 |
18 |
7 |
0.8 |
13.4 |
340 |
1.4 |
16.0 |
670 |
12.1 |
12 |
15 |
14 |
17 |
9 |
0.8 |
16.3 |
430 |
1.4 |
19.0 |
800 |
12.1 |
12 |
14 |
14 |
16 |
10 |
0.8 |
16.9 |
465 |
4x0.8 |
19.2 |
860 |
12.1 |
11 |
13 |
13 |
15 |
12 |
0.8 |
17.8 |
500 |
4x0.8 |
19.4 |
820 |
12.1 |
10 |
12 |
12 |
14 |
14 |
0.8 |
19.1 |
578 |
4x0.8 |
19.5 |
890 |
12.1 |
10 |
12 |
11 |
13 |
16 |
0.8 |
19.5 |
638 |
4x0.8 |
20.5 |
1000 |
12.1 |
9 |
11 |
11 |
12 |
19 |
0.8 |
22.0 |
710 |
4x0.8 |
21.8 |
1100 |
12.1 |
9 |
10 |
10 |
12 |
24 |
0.8 |
24.5 |
900 |
4x0.8 |
24.8 |
1330 |
12.1 |
8 |
10 |
9 |
11 |
|
Cables with stranded conductor can be made on request.
TABLE -2
2.5 Sq.mm., Solid Copper Conductor, PVC insulated, PVC Sheathed,
Unarmoured(YY)/Armoured (YWY & YFY), Multi Core
Control Cables - 650/ 1100 Volts Conforming to IS : 1554 (I) 1988
|
| |
|
|
Unarmoured |
Armoured |
Max DC
Conductor
Resistance
at 20* C
0hm/km |
A.C. Current Rating |
No.of
Crores |
Nominal
Thickness
of PVC
Insulation
mm |
Approx.
Over all Diameter
mm |
Approx.
Over all
Weight
kg/km |
Normal
steel
Armour
Size
mm
W F |
Approx.
Over all
Diameter
mm |
Approx.
Over all
Weight
kg/km |
In Air |
In Ground |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
2 |
0.9 |
12.0 |
210 |
1.4 |
14.6 |
460 |
7.41 |
27 |
32 |
32 |
37 |
3 |
0.9 |
12.5 |
250 |
1.4 |
15.0 |
490 |
7.41 |
24 |
29 |
27 |
31 |
4 |
0.9 |
14.0 |
280 |
1.4 |
15.8 |
580 |
7.41 |
24 |
29 |
27 |
32 |
5 |
0.9 |
14.5 |
310 |
1.4 |
17.0 |
600 |
7.41 |
19 |
23 |
23 |
27 |
6 |
0.9 |
15.2 |
360 |
1.4 |
18.4 |
740 |
7.41 |
18 |
21 |
21 |
25 |
7 |
0.9 |
15.2 |
380 |
1.4 |
18.4 |
770 |
7.41 |
17 |
20 |
20 |
23 |
9 |
0.9 |
19.0 |
490 |
1.4 |
20.1 |
810 |
7.41 |
16 |
19 |
19 |
22 |
10 |
0.9 |
19.3 |
610 |
4x0.8 |
20.0 |
90 |
7.41 |
15 |
18 |
18 |
20 |
12 |
0.9 |
20.1 |
710 |
4x0.8 |
20.6 |
1010 |
7.41 |
14 |
17 |
17 |
19 |
14 |
0.9 |
21.5 |
780 |
4x0.8 |
22.0 |
1100 |
7.41 |
13 |
16 |
16 |
18 |
16 |
0.9 |
22.5 |
880 |
4x0.8 |
22.5 |
1240 |
7.41 |
12 |
15 |
15 |
17 |
19 |
0.9 |
23.1 |
1020 |
4x0.8 |
25.0 |
1330 |
7.41 |
12 |
14 |
14 |
16 |
24 |
0.9 |
26.8 |
1260 |
4x0.8 |
28.5 |
1600 |
7.41 |
11 |
13 |
13 |
15 |
|
TABLE -3
2 Core, 3 Core & 4 Core Copper Conductor, PVC insulated, PVC
Sheathed, Unarmoured(YY)/ Armoured (YWY & YFY), Multi
Core Control Cables - 650/ 1100 Volts Conforming to IS : 1554 (I) 1988
|
No.of
Crores |
Nominal
Cores
Sectional
Area
Sq.mm |
Nominal
Thickness
Of PVC
Insulation
mm |
Unarmoured |
Armoured |
Max DC
Conductor
Resistance
at 20* C
0hm/km |
A.C. Current Rating |
Approx.
Over all Diameter
mm |
Approx.
Over all
Weight
kg/km |
Normal
steel
Armour
Size
mm
W F |
Approx.
Over all
Diameter
mm |
Approx.
Over all
Weight
kg/km |
In Air |
In Ground |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
2 |
4 |
1.0 |
13.00 |
280 |
1.4 |
15.5 |
630 |
4.61 |
35 |
43 |
41 |
48 |
2 |
6 |
1.0 |
14.00 |
380 |
1.4 |
16.8 |
770 |
3.08 |
45 |
55 |
50 |
58 |
2 |
10 |
1.0 |
15.60 |
510 |
1.4 |
19.4 |
950 |
1.83 |
60 |
73 |
70 |
81 |
2 |
16 |
1.0 |
16.60 |
690 |
4x0.8 |
20.8 |
1030 |
1.15 |
78 |
95 |
90 |
105 |
3 |
4 |
1.0 |
13.80 |
370 |
1.4 |
17.0 |
750 |
4.61 |
30 |
37 |
36 |
42 |
3 |
6 |
1.0 |
14.70 |
450 |
1.4 |
19.0 |
850 |
3.08 |
39 |
48 |
45 |
53 |
3 |
10 |
1.0 |
16.60 |
640 |
1.4 |
21.0 |
1100 |
1.83 |
52 |
63 |
60 |
69 |
3 |
16 |
1.0 |
17.90 |
870 |
4x0.8 |
22.4 |
1220 |
1.15 |
66 |
81 |
77 |
90 |
4 |
4 |
1.0 |
14.80 |
400 |
1.4 |
17.6 |
770 |
4.61 |
30 |
37 |
36 |
42 |
4 |
6 |
1.0 |
16.00 |
560 |
4x0.8 |
18.8 |
980 |
3.08 |
39 |
48 |
45 |
53 |
4 |
10 |
1.0 |
18.00 |
800 |
4x0.8 |
21.0 |
1110 |
1.83 |
52 |
63 |
60 |
69 |
4 |
16 |
1.0 |
20.40 |
1100 |
4x0.8 |
24.0 |
1400 |
1.15 |
66 |
81 |
77 |
90 |
|
NB:
4 & 6 Sq. mm cable are of Solid Conductor. While 10 & 16 Sq.
mm. cable are of Stranded or Secto Shaped. Conductor if
required, cable of 4 & 6 can be made with strandred conductor also.
|
TABLE-4
1 Core, Aluminium Conductor, PVC Insulated, PVC Sheathed, Unarmoured (AYY)/Armoured (AYAWY), Cables-650/1100 Volts |
| |
Nominal
Crores
Sectional
Area
Sq.mm |
Unarmoured |
Armoured |
Max DC
Conductor
Resistance
at 20* C
0hm/km |
A.C. Current Rating |
Nominal
Thickness
of
PVC
Insulation
mm |
Approx.
Over all
Diameter
mm |
Approx.
Weight
kg/km |
Normal
Thickness
of PVC
Insulation
mm |
Normal
Diameter
of wire
for
Armour
mm |
Approx.
Over all
Diameter
mm |
Approx.
Weight
kg/km |
In Air |
In Groung |
GPPVC
Insulation
2 3
Cables
Amps |
HRPVC
Insulation
2 3
Cables
Amps |
GPPVC
Insulation
2 3
Cables
Amps |
HRPVC
Insulation
2 3
Cables
Amps |
1.5 |
0.8 |
6.7 |
68 |
1.1 |
1.4 |
10.0 |
108 |
18.1 |
18 |
15 |
21 |
18 |
21 |
17 |
24 |
20 |
2.5 |
0.9 |
7.4 |
70 |
1.2 |
1.4 |
10.8 |
115 |
12.1 |
25 |
21 |
30 |
26 |
28 |
24 |
33 |
28 |
4.0 |
1.0 |
8.2 |
81 |
1.3 |
1.4 |
11.5 |
126 |
7.41 |
32 |
27 |
38 |
33 |
36 |
31 |
41 |
35 |
6.0 |
1.0 |
8.8 |
90 |
1.3 |
1.4 |
12.2 |
164 |
4.61 |
41 |
35 |
50 |
42 |
44 |
39 |
52 |
46 |
10 |
1.0 |
9.7 |
115 |
1.3 |
1.4 |
13.0 |
197 |
3.08 |
56 |
47 |
69 |
57 |
59 |
51 |
69 |
60 |
16 |
1.0 |
10.7 |
155 |
1.3 |
1.4 |
14.1 |
238 |
1.91 |
72 |
64 |
88 |
78 |
75 |
66 |
88 |
77 |
25 |
1.2 |
12.3 |
195 |
1.5 |
1.4 |
16.0 |
295 |
1.20 |
99 |
84 |
121 |
103 |
97 |
86 |
112 |
101 |
35 |
1.2 |
14.1 |
270 |
1.5 |
1.4 |
17.2 |
375 |
0.868 |
120 |
105 |
146 |
129 |
120 |
100 |
140 |
117 |
50 |
1.4 |
15.0 |
334 |
1.7 |
1.4 |
18.7 |
466 |
0.641 |
150 |
130 |
184 |
158 |
145 |
120 |
170 |
140 |
70 |
1.4 |
16.7 |
427 |
1.7 |
1.4 |
20.9 |
608 |
0.443 |
185 |
155 |
226 |
190 |
170 |
140 |
199 |
163 |
95 |
1.6 |
19.0 |
546 |
1.9 |
1.6 |
23.0 |
732 |
0.320 |
215 |
190 |
264 |
233 |
205 |
175 |
240 |
275 |
120 |
1.6 |
20.8 |
643 |
1.9 |
1.6 |
25.0 |
844 |
0.253 |
240 |
220 |
292 |
270 |
23 |
195 |
268 |
228 |
150 |
1.8 |
23.0 |
760 |
2.1 |
1.6 |
26.2 |
979 |
0.206 |
270 |
250 |
330 |
305 |
265 |
220 |
310 |
258 |
185 |
2.0 |
25.0 |
950 |
2.3 |
1.6 |
28.5 |
1151 |
0.164 |
305 |
290 |
374 |
356 |
300 |
240 |
351 |
278 |
240 |
2.2 |
28.0 |
1150 |
2.5 |
1.6 |
31.9 |
1429 |
0.125 |
350 |
335 |
430 |
410 |
335 |
270 |
392 |
316 |
300 |
2.4 |
32.0 |
1420 |
2.8 |
2.0 |
35.5 |
1784 |
0.100 |
395 |
380 |
484 |
464 |
370 |
295 |
434 |
345 |
400 |
2.6 |
35.5 |
1731 |
3.0 |
2.0 |
40.0 |
2226 |
0.0778 |
455 |
435 |
557 |
534 |
410 |
325 |
480 |
378 |
|
| |
Cables with copper conductor can be made on request.
TABLE-5
2 Core, Aluminium Conductor, PVC Insulated, PVC Sheathed, Unarmoured (AYY)/Armoured (AYWY & AYFY), Cables-650/1100 Volts |
| |
|
|
Unarmoured |
Armoured |
Max DC
Conductor
Resistactor
at 20*C
0hm/km |
A.C. Current Rating |
Nominal
Cores
Sectional
Area
Sq.mm |
Nominal
Thickness
of PVC
Insulation
mm |
Approx.
Over all
Diameter
mm |
Approx.
Over all Weight
kg/km |
Normal
Steel
Armour
Size
mm
W F |
Approx.
Over all
Diameter
mm |
Approx.
Over all
Weight
kg/km |
In Air |
In Ground |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
1.5 |
0.8 |
11.5 |
175 |
1.4 |
14.5 |
435 |
18.1 |
16 |
20 |
18 |
21 |
2.5 |
0.9 |
13.0 |
210 |
1.4 |
16.0 |
50 |
12.1 |
21 |
26 |
25 |
29 |
4.0 |
1.0 |
14.5 |
270 |
1.4 |
17.5 |
600 |
7.41 |
27 |
33 |
32 |
36 |
6.0 |
1.0 |
16.0 |
310 |
1.4 |
18.5 |
650 |
4.61 |
35 |
42 |
40 |
47 |
10 |
1.0 |
18.1 |
400 |
1.4 |
20.9 |
720 |
3.08 |
47 |
57 |
55 |
64 |
16 |
1.0 |
20.4 |
470 |
4x0.8 |
22.6 |
840 |
1.91 |
59 |
72 |
70 |
82 |
25 |
1.2 |
20.0 |
498 |
4x0.8 |
22.0 |
770 |
1.20 |
78 |
95 |
90 |
105 |
35 |
1.2 |
21.5 |
590 |
4x0.8 |
23.0 |
910 |
0.868 |
99 |
120 |
110 |
128 |
50 |
1.4 |
24.0 |
730 |
4x0.8 |
25.6 |
1100 |
0.641 |
125 |
153 |
135 |
158 |
70 |
1.4 |
26.5 |
880 |
4x0.8 |
28.0 |
1345 |
0.443 |
150 |
183 |
160 |
187 |
95 |
1.6 |
29.0 |
1190 |
4x0.8 |
30.6 |
1685 |
0.320 |
185 |
225 |
190 |
222 |
120 |
1.9 |
31.9 |
1350 |
4x0.8 |
33.5 |
1890 |
0.253 |
210 |
256 |
210 |
245 |
150 |
1.8 |
35.0 |
1650 |
4x0.8 |
36.0 |
2265 |
0.206 |
240 |
294 |
240 |
280 |
185 |
2.0 |
37.3 |
1950 |
4x0.8 |
39.8 |
2685 |
0.164 |
275 |
337 |
275 |
322 |
240 |
2.2 |
43.7 |
2500 |
4x0.8 |
45.7 |
3400 |
0.125 |
325 |
397 |
320 |
374 |
300 |
2.4 |
45.8 |
3100 |
4x0.8 |
47.6 |
4030 |
0.100 |
365 |
445 |
355 |
416 |
400 |
2.6 |
51.0 |
4000 |
4x0.8 |
52.5 |
4950 |
0.0778 |
420 |
515 |
385 |
450 |
|
Cables with conductor area upto 10sq. mm. can be substituted with copper, of one size lower. |
| |
TABLE-6
3 Core, Aluminium Conductor, PVC Insulated, PVC Sheathed, Unarmoured (AYY)/Armoured (AYWY), Cables-650/1100 Volts |
| |
|
|
Unarmoured |
Armoured |
Max DC
Conductor
Resistactor
at 20*C
0hm/km |
A.C. Current Rating |
Nominal
Cores
Sectional
Area
Sq.mm |
Nominal
Thickness
of PVC
Insulation
mm |
Approx.
Over all
Diameter
mm |
Approx.
Over all
Weight
kg/km |
Normal
Steel
Armour
Size
mm
W F |
Approx.
Over all
Diameter
mm |
Approx.
Weight
kg/km |
In Air |
In Ground |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
1.5 |
0.8 |
11.5 |
200 |
1.4 |
14.5 |
485 |
18.100 |
13 |
16 |
16 |
18 |
2.5 |
0.9 |
13.0 |
240 |
1.4 |
16.0 |
560 |
12.1000 |
18 |
22 |
21 |
24 |
4.0 |
1.0 |
15.4 |
290 |
1.4 |
17.5 |
610 |
7.4100 |
23 |
28 |
28 |
32 |
6.0 |
1.0 |
16.5 |
338 |
1.4 |
19.0 |
690 |
4.6100 |
30 |
38 |
35 |
41 |
10 |
1.0 |
18.5 |
420 |
4x0.8 |
22.5 |
850 |
3.0800 |
40 |
49 |
46 |
54 |
16 |
1.0 |
21.2 |
560 |
4x0.8 |
23.0 |
970 |
1.9100 |
51 |
63 |
60 |
69 |
25 |
1.2 |
22.0 |
620 |
4x0.8 |
23.5 |
1050 |
1.2000 |
70 |
86 |
76 |
89 |
35 |
1.2 |
24.0 |
770 |
4x0.8 |
23.5 |
1145 |
0.8680 |
86 |
105 |
92 |
108 |
50 |
1.4 |
27.5 |
970 |
4x0.8 |
29.0 |
1450 |
0.6410 |
105 |
127 |
110 |
129 |
70 |
1.4 |
30.5 |
1270 |
4x0.8 |
31.5 |
1700 |
0.4430 |
130 |
159 |
135 |
157 |
95 |
1.6 |
34.5 |
1640 |
4x0.8 |
36.0 |
2200 |
0.3200 |
155 |
190 |
165 |
193 |
120 |
1.9 |
37.0 |
1865 |
4x0.8 |
38.5 |
2490 |
0.2530 |
180 |
218 |
185 |
215 |
150 |
1.8 |
40.8 |
2370 |
4x0.8 |
42.8 |
3080 |
0.2060 |
205 |
251 |
210 |
246 |
185 |
2.0 |
45.2 |
2875 |
4x0.8 |
46.8 |
3615 |
0.1640 |
240 |
294 |
235 |
276 |
240 |
2.2 |
50.6 |
3820 |
4x0.8 |
52.5 |
4550 |
0.1250 |
280 |
340 |
275 |
322 |
300 |
2.4 |
58.5 |
4635 |
4x0.8 |
59.5 |
5500 |
0.1000 |
315 |
386 |
305 |
358 |
400 |
2.6 |
63.3 |
5600 |
4x0.8 |
65.0 |
6700 |
0.0778 |
375 |
445 |
335 |
390 |
|
Cables with conductor area upto 10sq.mm. can be substituted with copper
conductor, of one size lower. Constructional details of 3x500 and 3x630
sq.mm. will be provided on specific request.
TABLE-7
3 1/2 Core, Aluminium Conductor, PVC Insulated, PVC Sheathed, Unarmoured (AYY)/Armoured (AYWY), Cables-650/1100 Volts |
| |
|
|
Unarmoured |
Armoured |
Max DC
Conductor
Resistactor
at 20*C
0hm/km |
A.C. Current Rating |
Nominal
Cores
Sectional
Area
Sq.mm |
Nominal
Thickness
of PVC
Insulation
mm |
Approx.
Over all
Diameter
mm |
Approx.
Over all
Weight
kg/km |
Normal
Steel
Armour
Size
mm
W F |
Approx.
Over all
Diameter
mm |
Approx.
Weight
kg/km |
In Air |
In Ground |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
25 |
1.2 |
25.0 |
760 |
4x0.8 |
23.0 |
1050 |
1.2000 |
70 |
86 |
76 |
89 |
35 |
1.2 |
27.5 |
880 |
4x0.8 |
25.3 |
1221 |
0.8680 |
86 |
105 |
92 |
108 |
50 |
1.4 |
30.0 |
1145 |
4x0.8 |
29.5 |
1500 |
0.6410 |
105 |
127 |
110 |
129 |
70 |
1.4 |
34.5 |
1470 |
4x0.8 |
32.8 |
2000 |
0.4430 |
130 |
159 |
135 |
157 |
95 |
1.6 |
38.5 |
1890 |
4x0.8 |
37.2 |
2200 |
0.3200 |
155 |
190 |
165 |
193 |
120 |
1.6 |
42.0 |
2300 |
4x0.8 |
40.5 |
2600 |
0.2530 |
180 |
218 |
185 |
215 |
150 |
1.8 |
46.0 |
2710 |
4x0.8 |
45.0 |
3100 |
0.2060 |
205 |
251 |
210 |
246 |
185 |
2.0 |
50.2 |
3210 |
4x0.8 |
49.5 |
3800 |
0.1640 |
240 |
294 |
235 |
276 |
240 |
2.2 |
56.5 |
4230 |
4x0.8 |
55.6 |
4800 |
0.1250 |
280 |
340 |
275 |
322 |
300 |
2.4 |
62.5 |
5385 |
4x0.8 |
61.5 |
5800 |
0.1000 |
315 |
386 |
305 |
358 |
400 |
2.6 |
69.5 |
6650 |
4x0.8 |
69.5 |
7500 |
0.0778 |
375 |
445 |
335 |
390 |
|
Constructional details of 3 1/2x500 and 3 1/2x630 sq.mm. will be provided on specific request.
TABLE-8
4 Core, Aluminium Conductor, PVC Insulated, PVC Sheathed, Unarmoured (AYY)/Armoured (AYWY & AYFY), Cables-650/1100 Volts |
| |
|
|
Unarmoured |
Armoured |
Max DC
Conductor
Resistactor
at 20*C
0hm/km |
A.C. Current Rating |
Nominal
Cores
Sectional
Area
Sq.mm |
Nominal
Thickness
of PVC
Insulation
mm |
Approx.
Over all
Diameter
mm |
Approx.
Over all
Weight
kg/km |
Normal
Steel
Armour
Size
mm
W F |
Approx.
Over all
Diameter
mm |
Approx.
Weight
kg/km |
In Air |
In Ground |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
GPPVC
Insulation
Amps |
HRPVC
Insulation
Amps |
2.5 |
0.9 |
14.0 |
230 |
1.4 |
17.0 |
560 |
12.100 |
18 |
22 |
21 |
24 |
4.0 |
1.0 |
16.6 |
320 |
1.4 |
19.0 |
700 |
7.4100 |
23 |
28 |
28 |
32 |
6.0 |
1.0 |
18.0 |
350 |
4x0.8 |
20.5 |
800 |
4.6100 |
30 |
38 |
35 |
41 |
10. |
1.0 |
20.0 |
450 |
4x0.8 |
21.0 |
810 |
3.0800 |
40 |
49 |
46 |
54 |
16 |
1.0 |
23.0 |
650 |
4x0.8 |
23.5 |
1000 |
1.9100 |
51 |
63 |
60 |
69 |
25 |
1.2 |
25.5 |
765 |
4x0.8 |
26.0 |
1210 |
1.2000 |
70 |
86 |
76 |
89 |
35 |
1.2 |
28.0 |
930 |
4x0.8 |
28.5 |
1420 |
0.8680 |
86 |
105 |
92 |
108 |
50 |
1.4 |
32.9 |
1250 |
4x0.8 |
34.0 |
1800 |
0.6410 |
105 |
127 |
110 |
129 |
70 |
1.4 |
36.4 |
1600 |
4x0.8 |
37.5 |
2220 |
0.4430 |
130 |
159 |
135 |
157 |
95 |
1.6 |
41.3 |
2180 |
4x0.8 |
42.5 |
2830 |
0.3200 |
155 |
190 |
165 |
193 |
120 |
1.6 |
44.8 |
2560 |
4x0.8 |
45.0 |
3250 |
0.2530 |
180 |
218 |
185 |
215 |
150 |
1.8 |
49.7 |
3120 |
4x0.8 |
51.0 |
3920 |
0.2060 |
205 |
251 |
210 |
246 |
185 |
2.0 |
54.6 |
3700 |
4x0.8 |
56.2 |
4550 |
0.1640 |
240 |
294 |
235 |
276 |
240 |
2.2 |
61.0 |
4760 |
4x0.8 |
63.0 |
5930 |
0.1250 |
280 |
340 |
275 |
322 |
300 |
2.4 |
67.0 |
5900 |
4x0.8 |
68.5 |
6970 |
0.1000 |
315 |
386 |
305 |
358 |
400 |
2.6 |
76.2 |
7425 |
4x0.8 |
78.0 |
8800 |
0.0778 |
375 |
445 |
335 |
390 |
|
| |
Cables with conductor area upto 10sq. mm. can be substituted with copper conductor, of one size lower.
Note:- As per the International Practice which is also approved by BIS.
The size of conductor decide by its Resistance only. |
|
|
|