Premium building wires designed for safe and dependable fixed electrical installations in residential, commercial, and industrial buildings. Featuring flexible, EC-grade copper conductors with high-quality PVC insulation (FR/FRLS/ZHFR), these cables offer superior flame retardance, moisture resistance, and electrical performance up to 1100 V. Ideal for concealed wiring, lighting circuits, power distribution and appliances, they meet international standards and ensure long-lasting safety and reliability.
High flame retardant properties
| Nominal cross section area of conductor | Number / Nominal dia of strands | Nominal Insulation Thickness | Approx Overall Diameter | Max. Conductor Resistance at 20°C | Current Rating | |
|---|---|---|---|---|---|---|
| Sq. mm | mm | mm | mm | ohm/km | Casing AMPS | Concealed AMPS |
| 1.00 | 14/0.30* | 0.70 | 2.80 | 18.1 | 14 | 13 |
| 1.50 | 22/0.30* | 0.70 | 3.00 | 12.1 | 18 | 16 |
| 2.50 | 36/0.30* | 0.80 | 3.70 | 7.41 | 24 | 20 |
| 4.00 | 56/0.30** | 0.80 | 4.20 | 4.95 | 32 | 26 |
| 6.00 | 84/0.30** | 0.80 | 4.80 | 3.30 | 42 | 35 |
* Class 2 Stranded conductor
** Class 5 Flexible conductor
| Test | Specified | Specified Values |
|---|---|---|
| Limited Oxygen Index Test | IS 10810-58 | > 29% |
| Limited Temperature Index Test | IS 10810-65 | > 250% |
| Test | Specified | Specified Values |
|---|---|---|
| Limited Oxygen Index Test | ASTM-D 2863 | > 32% |
| Limited Temperature Index Test | ASTM-D 2863 | > 250% |
| Smoke Density (Light Absorption) | ASTM-D 2863 | > 50% |
| Acid Gas Generation | 1 EC-607 54-1 | > 18% |
| Cross Sectional Area Sq. mm. | Copper Construction Nos./mm | Nominal Thickness mm | Maximum Overall Diameter mm | Maximum Conductor Resistance at 20°C Ω/km | Current rating at 40°C Amps | |
|---|---|---|---|---|---|---|
| Casing | Concealed | |||||
| 0.75 | 24/0.200 | 0.60 | 2.80 | 26.00 | 10 | 9 |
| 1.00 | 32/0.200 | 0.60 | 3.00 | 19.50 | 14 | 13 |
| 1.50 | 30/0.250 | 0.60 | 3.40 | 13.30 | 18 | 16 |
| 2.50 | 50/0.250 | 0.70 | 4.10 | 7.98 | 24 | 20 |
| 4.00 | 56/0.300 | 0.80 | 4.80 | 4.95 | 32 | 26 |
| 6.00 | 84/0.300 | 0.80 | 5.30 | 3.30 | 42 | 35 |
| FRLF PVC INSULATED FLEXIBLE CABLES | |
|---|---|
| Cable Structure | Cable Features |
| Conductor: ABC / ATC | Temperature Range: -15°C to 70°C |
| Insulation: PVC Type A / D FR as per IS 5831 | Flame Retardant |
| Core Colours: Red, Black, Yellow, Blue, White, Grey | Voltage Grade: Up to and including 1100V |
| Test | Test method | Value |
|---|---|---|
| Limited Oxygen Index | IS 10810 P-58 | > 29% |
| Limited Temperature Index | IS 10810 P-64 | > 250°C |
| Cable Structure | Cable Features |
|---|---|
| Conductor: ABC / ATC | Temperature Range: -15°C to 70°C |
| Insulation: PVC Type A / D FR-LSH as per IS 5831 | Flame Retardant and low smoke |
| Core Colours: Red, Black, Yellow, Blue, White, Grey | Voltage Grade: Up to and including 1100V |
| Produces less toxic and corrosive gases | |
| Durable, moisture and abrasion resistant |
| Test | Test method | Value |
|---|---|---|
| Limited Oxygen Index | IS 10810 P-58 | > 29% |
| Limited Temperature Index | IS 10810 P-64 | > 250°C |
| Smoke Density Rating | IS 13360 P-6/Sec-9 | < 60% |
| Halogen Acid gas Evolution | IS 10810 P-59 | < 20% |
| Cable Structure | Cable Features |
|---|---|
| Conductor: ABC / ATC | Temperature range: -15°C to 85°C |
| Insulation: PVC Type C as per IS 5831 | Heat Resistance |
| Voltage Grade: Up to and including 1100V | Thermal Resistance |
| Core Colours: Red, Black, Yellow, Blue, White, Grey, Green Yellow | Voltage Grade: Up to and including 1100V |
| Self-extinguishing and flame retardant |
| Cable Structure | Cable Features |
|---|---|
| Conductor: ABC / ATC | Temperature range: -15°C to 70°C |
| Insulation: Thermoplastic HFFR as per IS 17048 | Voltage Grade: Up to and including 1100V |
| Voltage Grade: Up to and including 1100V | Smoke is negligible, transparent, non-toxic |
| Core Colours: Red, Black, Yellow, Blue, White, Grey, Green Yellow | Self-extinguishing and flame retardant according to IS 10810 P-61 |
| The cable is also ozone resistant |
| Test | Test method | Value |
|---|---|---|
| pH | IS 17048 | ≥ 4.3 |
| Conductivity | IS 17048 | ≤ 10 μS/mm |
| Chlorine and bromine expressed as content of HCL | IS 10810 P-59 | ≤ 0.5 % |
| Presence of fluorine | IS 17048 | ≤ 0.1 % |
The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
In view of continuous improvements in our design and process, specifications given here in are subject change without notice.